text.skipToContent text.skipToNavigation

AA990CEGQJGBB100M

EDGE™ RC Indoor Breakout Trunk - MTP to MTP  864F, 24F MTP connector (Non-Pinned) to 12F MTP connector (Non-pinned), Indoor RocketRibbon® Riser/LSZH Cable, Pulling grip on 24F MTP end, 100 meters

Contact Distributor for Lead Time

General Specifications
Product Number AA990CEGQJGBB100M
Fiber Category Single-Mode (OS2) Ultra
Environment Indoor
Application Data Center LAN/SAN 
Cable Type Indoor UltraRibbon™ Riser
Brand EDGE™
Standards
RoHS Free of hazardous substances according to RoHS 2011/65/EU
Environmental Conditions
Temperature Range, Installation -10 °C  to  60 °C    (14 °F  to  140 °F    )
Temperature Range, Operation -20 °C  to  70 °C    (-4 °F  to  158 °F    )
Temperature Range, Storage -40 °C  to  70 °C    (-40 °F  to  158 °F    )
Design
Fiber Count 864
Polarity Type B
Fiber Type Single-mode
Mechanical Specifications
Nominal Outer Diameter 22.8 mm 
Min. Bend Radius Installation 300 mm
Min. Bend Radius Operation 300 mm
Specifications - Connector A
Reflectance, Typical < -60 dB
Insertion Loss, Max. 0.35 dB
Connector Type 24 F MTP® (non-pinned)
Ferrule Material Composite
Reflectance < -60 dB
Specifications - Connector B
Reflectance, Typical < -60 dB
Insertion Loss, Max. 0.35 dB
Connector Type 12 F MTP® (non-pinned)
Ferrule Material Composite
Reflectance < -60 dB
Furcation - Connector A
Leg Length 1320.8 mm
Furcation Type Single Furcation
Leg Color Yellow
Shortest Staggering Leg Length (mm) 1.22 mm
Furcation - Connector B
Furcation Type Single Furcation
Leg Color Yellow
Shortest Staggering Leg Length (mm) 914 mm
Leg Length 914.4 mm
Pulling Grip - Connector A
Pulling grip Yes
Grip Outer Diameter 89 mm
Pulling Grip - Connector B
Pulling grip Protective only
Dimensions
Length 100 ft
Height 101 mm
Cable Weight 455 kg/km
Ordering Information
Units per Delivery 1/1
Reduced Installation Time
EDGE RC allows the installer to remove splicing in the field, increasing speed of deployment by up to 70%.
Solution flexibility
Allows a flexible path to connectivity with MTP and LC configurations.
Factory Termination
Results in quicker deployment and better performance while reducing risks associated with field installation, rework, or high insertion loss.