General Specifications
Product Number | 864ZZZ-14161B20 |
EAN Code | 4099802348768 |
Fiber Category | G.657.A1 190 |
Flame Rating | Riser/LSZH (OFNR-LS) |
Cable geometry | Round |
Standards
Reaction to Fire | Cca, s1, d1, a1 |
RoHS | Free of hazardous substances according to RoHS 2011/65/EU |
Reaction to Fire Requirements | Reaction to fire according to EN 50575 and EN 13501-6 |
Environmental Conditions
Temperature Range, Installation | -10 °C to 60 °C (14 °F to 140 °F ) |
Temperature Range, Operation | -40 °C to 70 °C (-40 °F to 158 °F ) |
Temperature Range, Storage | -40 °C to 70 °C (-40 °F to 158 °F ) |
Cable Design
Fiber Count | 864 |
Outer Jacket Color | Black |
Outer Jacket Material | Polyethylene (FRNC/LSZH) |
Tape | Water-swellable |
Mechanical Specifications
Max. Tensile Strength, Long-Term | 800 N (179.85 lbf) |
Max. Tensile Strength, Short-Term | 2700 N (606.98 lbf) |
Nominal Outer Diameter | 14.5 mm (0.57 in ) |
Min. Bend Diameter Operation | 480 mm (18.9 in) |
Min. Bend Diameter Installation | 640 mm (25.2 in) |
Optical Characteristics
Fiber Code | Z |
Fiber Name | G.657.A1 Optical fiber with 190-micron outer diameter |
Fiber Type | Single-mode |
Fiber Compliance | ITU-T G.652.D and ITU-T G.657.A1 |
Performance Option Code | 61 |
Cladding diameter | 125 µm |
Maximum Attenuation | 0.4 dB/km / 0.4 dB/km / 0.3 dB/km |
Mode-Field Diameter at 1310 nm | 9.2 µm |
Wavelengths | 1310 nm / 1550 nm |
PMD maximum individual fiber | ≤ 0.1 ps/(nm*km) |
Coating diameter | 188 µm |
Fiber Category | G.652.D/G.657.A1 |
Dimensions
Cable Weight | 197 kg/km (132.38 lb/1000 ft) |
Bend-Improved Single-mode 190 μm Diameter
ITU-T G.652.D and G.657.A1-compliant 190 micron single-mode fiber with a 9.2 μm MFD maintains full compatibility with existing fiber networks
Flow Ribbon Technology
Allows for smaller cable designs and easier routing in hardware. Flow Ribbons are compatible with both 200 μm and 250 μm commercially available splicers
Reduced Cable Diameter
High fiber density in microduct systems. Up to 57% reduction in cable diameter (compared to existing SST-UltraRibbon™) doubling fiber count per duct at similar ODs
Optimized for air-assisted install in microducts
Capable of long installation distances
Indoor/Outdoor Jacket
Eliminates the need for a transitionsplice at building entry.
Dual Flame Rated
Allows cable to be used anywhere around the globe