text.skipToContent text.skipToNavigation

G907836GPNDLW100F

EDGE™ Hybrid Trunk  36F, Bend-Improved single-mode (OS2), 100 ft

Contact Distributor for Lead Time

General Specifications
Product Number G907836GPNDLW100F
Flame Rating Plenum (OFNP)
Fiber Category Bend-improved SM (OS2)
Cable Assembly Type EDGE™ Trunk
Environment Indoor
Application Data Center 
Connector Assembly Type MTP to LC
Standards
RoHS Free of hazardous substances according to RoHS 2011/65/EU
Approvals and Listings NFPA 262, National Electrical Code® (NEC®), OFNP, CSA FT-6 
Design and Test Criteria ANSI/ICEA S-83-596 
Environmental Conditions
Temperature Range, Operation -10 °C  to  60 °C    (14 °F  to  140 °F    )
Design
Fiber Count 36
Polarity Universal hybrid
Fiber Type Single-mode
Mechanical Specifications
Nominal Outer Diameter 8 mm  (0.31 in )
Weight 56 kg/km (37.63 lb/1000 ft)
Minimum Conduit Size with 18-in Elbow 64 mm (2.52 in)
Specifications - Connector A
Insertion Loss, Max. 0.35 dB
Boot Color Black
Connector Type MTP® (non-pinned)
Ferrule Material Composite
Reflectance < -65 dB
Specifications - Connector B
Insertion Loss, Max. 0.25 dB
Boot Color Blue
Connector Type LC Uniboot
Ferrule Material Ceramic
Reflectance < -55 dB
Pulling Grip - Connector A
Pulling grip Yes
Tensile Strength 440 N (98.92 lbf)
Dimensions
Length 100 ft
Cable Weight 56 kg/km (37.63 lb/1000 ft)
Ordering Information
Packaging Method Plastic reel
Furcation - Connector A
Leg Length 838 mm (32.99 in)
Furcation Type EDGE™ Size 1, 14.7 mm x 14.7 mm x 108.6 mm
Leg Color Yellow
Leg Diameter 2 mm (0.08 in)
Leg Count 3
Furcation - Connector B
Furcation Type EDGE™ Size 2, 20 mm x 20 mm x 108.6 mm
Leg Color Yellow
Leg Diameter 2 mm (0.08 in)
Leg Count 18
Leg Length 914 mm (35.98 in)
Snap-in strain-relief clips
Provide easier cable management
Small outer diameter
Improves cable tray fill ratio and allows for imported airflow
Low-loss connectivity
Enables system design flexibility
Bend-improved fiber
Allows tighter cable bends for slack storage and routing, less risk of downtime due to pinched or bent cables
Corning® CleanAdvantage™ technology and optimized dust cap
Eliminates the need for scoping and cleaning prior to initial field connection